Studies of Flammable Liquid Boilover at Low Pressure and High Altitude
- 作者: Ding C.1, Wang X.J.1, Li H.2
-
隶属关系:
- State Key Laboratory of Fire Science, University of Science and Technology of China
- Safety Engineering Institute, College of Quality and Safety Engineering, China Jiliang University
- 期: 卷 55, 编号 3 (2019)
- 页面: 310-318
- 栏目: Article
- URL: https://journal-vniispk.ru/0009-3092/article/view/235857
- DOI: https://doi.org/10.1007/s10553-019-01034-4
- ID: 235857
如何引用文章
详细
Contact of a flammable liquid and water can cause hazardous boilover because of their different boiling points. The dependence of the initial boilover point of a flammable liquid on atmospheric pressure was studied at different geographic locations with different altitudes, i.e., at HeFei (alt., 0 m; P, 101 kPa) and on Lhasa plateau (alt., 3650 m; P, 64 kPa). The temperatures in the bulk and at the interface of the flammable liquid and water, flame temperature, thermal radiation, sound level, and mass loss at ambient temperature were experimentally measured using identical transparent quartz pans for each measurement. The experimental results showed that boilover was delayed or diminished at low pressure and disappeared completely at pressures lower than a certain critical value for this pan surface area. The pan size was shown not to affect the boilover onset or intensity.
作者简介
Chao Ding
State Key Laboratory of Fire Science, University of Science and Technology of China
编辑信件的主要联系方式.
Email: dc707@ustc.edu.cn
中国, HeFei
Xiao Wang
State Key Laboratory of Fire Science, University of Science and Technology of China
Email: dc707@ustc.edu.cn
中国, HeFei
Haihang Li
Safety Engineering Institute, College of Quality and Safety Engineering, China Jiliang University
Email: dc707@ustc.edu.cn
中国, Hangzhou