Switching of High-Voltage Cable Lines with Shunt Reactors


如何引用文章

全文:

开放存取 开放存取
受限制的访问 ##reader.subscriptionAccessGranted##
受限制的访问 订阅存取

详细

The problem of disconnecting high-voltage cable lines with shunt reactors by SF6 circuit breakers is discussed. In these schemes it is possible to have a significant aperiodic component of the circuit breaker current that can prevent opening of the breaker. The authors propose methods for application to cable transmission lines which they believe will be optimal for ensuring normal disconnects.