Analysis of the Trip of a High-Power Turbine-Generator of a Nuclear Power Plant Upon Damage of the Stator Winding Insulation According to Data of Monitoring and Modeling
- Authors: Krutikov K.K.1, Rozhkov V.V.1, Butrimov S.G.2, Ivanov V.N.2, Ponkratenko A.O.2
-
Affiliations:
- Branch of the Moscow Power Engineering Institute in Smolensk
- Smolensk Nuclear Power Plant
- Issue: Vol 52, No 4 (2018)
- Pages: 451-460
- Section: Power Systems and Electric Networks
- URL: https://journal-vniispk.ru/1570-145X/article/view/246258
- DOI: https://doi.org/10.1007/s10749-018-0974-5
- ID: 246258
Cite item
Abstract
The operating conditions of a turbine-generator with the stator winding short-circuited to the frame are analyzed. The features of the shape of the zero-sequence voltage during arcing in the damaged gap are described. The operation of the relay protection in these conditions is analyzed. The real oscillograms of the subsequent suppression of the rotor field are theoretically justified. It is shown that improving the thyristor excitation system is necessary and possible.
About the authors
K. K. Krutikov
Branch of the Moscow Power Engineering Institute in Smolensk
Email: umo@sbmpei.ru
Russian Federation, Smolensk
V. V. Rozhkov
Branch of the Moscow Power Engineering Institute in Smolensk
Author for correspondence.
Email: umo@sbmpei.ru
Russian Federation, Smolensk
S. G. Butrimov
Smolensk Nuclear Power Plant
Email: umo@sbmpei.ru
Russian Federation, Desnogorsk, Smolensk Oblast’
V. N. Ivanov
Smolensk Nuclear Power Plant
Email: umo@sbmpei.ru
Russian Federation, Desnogorsk, Smolensk Oblast’
A. O. Ponkratenko
Smolensk Nuclear Power Plant
Email: umo@sbmpei.ru
Russian Federation, Desnogorsk, Smolensk Oblast’
Supplementary files