Phase Wire Break Signaling for 6 – 10 kV Overhead Line
- Авторлар: Ershov A.M.1, Khlopova A.B.1, Sidorov A.I.1
-
Мекемелер:
- South Ural State University
- Шығарылым: Том 52, № 1 (2018)
- Беттер: 110-115
- Бөлім: Article
- URL: https://journal-vniispk.ru/1570-145X/article/view/246104
- DOI: https://doi.org/10.1007/s10749-018-0918-0
- ID: 246104
Дәйексөз келтіру
Аннотация
To detect phase wire breaks in a 6 – 10 kV overhead line, the negative-sequence voltage on the low-tension side of the 6 – 10/0.4 kV power transformer can be used. The results of studying the effect of a phase wire break in an overhead line, phase displacement groups, and phase unbalance of demand loads in a 380 V network on the negative-sequence voltage are presented. A device for signaling phase wire breaks in a 6 – 10 kV overhead line is described. The device is based on a microprocessor electricity meter installed on the low-tension side of a 6 – 10/0.4 kV power transformer.
Негізгі сөздер
Авторлар туралы
A. Ershov
South Ural State University
Хат алмасуға жауапты Автор.
Email: a.m.ershov@mail.ru
Ресей, Chelyabinsk
A. Khlopova
South Ural State University
Email: a.m.ershov@mail.ru
Ресей, Chelyabinsk
A. Sidorov
South Ural State University
Email: a.m.ershov@mail.ru
Ресей, Chelyabinsk
Қосымша файлдар
