A Possibility of Reducing the Induced Voltage Within a Repair Area1
- Авторы: Monakhov A.F.1, Degtyarenko E.A.1, Danilov D.B.1
-
Учреждения:
- National Research University “Moscow Power Engineering Institute”
- Выпуск: Том 50, № 3 (2016)
- Страницы: 329-331
- Раздел: Power Systems and Electric Networks
- URL: https://journal-vniispk.ru/1570-145X/article/view/245245
- DOI: https://doi.org/10.1007/s10749-016-0706-7
- ID: 245245
Цитировать
Аннотация
The electromagnetic effect of a live high-voltage line on a disconnected line is analyzed. It is shown by calculation that the zero-potential point of the disabled conductor can be shifted to the repair area by changing the grounding resistance at the substations. To this end, adjustable resistors placed between the disabled conductor and the grounding devices at the substations can be used. The possibility of automating this process is examined.