The Effect of Current-Limiting Reactors on the Tripping of Short Circuits in High-Voltage Electrical Equipment
- 作者: Volkov M.S.1, Gusev Y.P.1, Monakov Y.V.1, Cho G.C.1
-
隶属关系:
- National Research University “Moscow Power Engineering Institute,”
- 期: 卷 49, 编号 5 (2016)
- 页面: 375-377
- 栏目: Article
- URL: https://journal-vniispk.ru/1570-145X/article/view/244964
- DOI: https://doi.org/10.1007/s10749-016-0631-9
- ID: 244964
如何引用文章
详细
The insertion of current-limiting reactors into electrical equipment operating at a voltage of 110 and 220 kV produces a change in the parameters of the transient recovery voltages at the contacts of the circuit breakers for disconnecting short circuits, which could be the reason for the increase in the duration of the short circuit, damage to the electrical equipment and losses in the power system. The results of mathematical modeling of the transients, caused by tripping of the short circuit in a reactive electric power transmission line are presented, and data are given on the negative effect of a current-limiting resistor on the rate of increase and peak value of the transient recovery voltages. Methods of ensuring the standard requirements imposed on the parameters of the transient recovery voltages when using current-limiting reactors in the high-voltage electrical equipment of power plants and substations are proposed and analyzed.
作者简介
M. Volkov
National Research University “Moscow Power Engineering Institute,”
Email: el.stantsii@gmail.com
俄罗斯联邦, Moscow
Yu. Gusev
National Research University “Moscow Power Engineering Institute,”
Email: el.stantsii@gmail.com
俄罗斯联邦, Moscow
Yu. Monakov
National Research University “Moscow Power Engineering Institute,”
Email: el.stantsii@gmail.com
俄罗斯联邦, Moscow
Gvan Cho
National Research University “Moscow Power Engineering Institute,”
Email: el.stantsii@gmail.com
俄罗斯联邦, Moscow
补充文件