Investigation of Heat Pump Efficiency on Zeotropic Refrigerants R32/R134a and R32/R152a


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

Results of analysis of thermodynamic cycle efficiency with consideration of nonisothermal nature of phase transition indicate that when using the mixture of R32/R152a (30/70%) in the vapor compression heat pumps, the coefficient of performance is up to 4% higher in comparison with R32/R134a (30/70%). The study shows that in cycles with two-stage compression the coefficient of performance increases by 6.5% as compared to the single-stage process. The value of exergic efficiency of the single-stage cycle is equal to 0.47 for zeotropic mixture of R32/R152a (30/70%), and it is equal to 0.45 for the R32/R134a (30/70%) mixture. Data obtained for the zeotropic mixtures are as effective as those obtained for refrigerant R134a.

About the authors

N. N. Mezentseva

Kutateladze Institute of Thermophysics, Siberian Branch

Author for correspondence.
Email: mnn@itp.nsc.ru
Russian Federation, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090

I. V. Mezentsev

Kutateladze Institute of Thermophysics, Siberian Branch

Email: mnn@itp.nsc.ru
Russian Federation, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090