Desorption of Aqueous Solution of Lithium Bromide on Enhanced Surfaces in a Single-Stage Lithium-Bromide Absorption Chiller


Cite item

Full Text

Open Access Open Access
Restricted Access Access granted
Restricted Access Subscription Access

Abstract

This article presents values of heat transfer coefficients at pool boiling of aqueous solution of lithium bromide on smooth and fin tubes. The experimental studies were performed under conditions typical of absorption chiller with single-stage desorption. More exactly, the condensation pressure was about 7.8–8.5 kPa, and the concentration of lithium bromide solution was 60–61 wt%. The outer diameter of the smooth and fin tubes was 16.0 mm; the inner diameter was 12.0 mm. The surface roughness factor of the fin tubes ranged from 2.7 to 6.0. The studies have shown that for fin tubes the heat transfer coefficient reduced to a surface unit is up to 30 percent higher as compared with a smooth tube.

About the authors

K. Stepanov

Kutateladze Institute of Thermophysics, Siberian Branch

Author for correspondence.
Email: stepanov_ki@mail.ru
Russian Federation, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090

D. Mukhin

Kutateladze Institute of Thermophysics, Siberian Branch

Email: stepanov_ki@mail.ru
Russian Federation, pr. Akad. Lavrent’eva 1, Novosibirsk, 630090

N. Zubkov

Bauman Moscow State Technical University

Email: stepanov_ki@mail.ru
Russian Federation, ul. 2aya Baumanskaya 5, Moscow, 105005

Supplementary files

Supplementary Files
Action
1. JATS XML

Copyright (c) 2019 Pleiades Publishing, Ltd.